IntelliPULSE™ (Timer)
Architecture: |
Robust modular DIN rail, CAN Open bus with 32 bit DSP |
Power Supply: |
97-132VAC 50/60Hz, 10VA max, no loads |
|
195 - 264VAC 50/60Hz, 10VA max, no loads |
|
20-28VDC, 10Watts max, no loads |
Solenoid Outputs: |
8-64 outputs (8 channel snap-in modules, status LEDs, front mounted fuse)
Solid state intelligent triac with protective snubber circuit
(Refer to B-PAC™ Controls for over 64 rows) |
Timing: |
0.01 - 2.0 sec On time, 3.0 - 600.0 sec Off time
Ontime synchronized to AC line |
User Interface: |
2.7" 128x64 pixel OLED graphic, 32 bit ARM, membrane keypad |
Temperature: |
-40F (-40C) to +160F (+70C) operating |
Inputs/Outputs (Std): |
(2) Alarm output 5A 240VAC resistive
(2) Alarm input 120VAC 50/60Hz, 5.4mA |
Additional I/O (Opt): |
(1) 4 Channel discrete mode/function control module, 120VAC
(1) Isolated 4-20mA output |
Field Bus (Opt): |
Ethernet IP, Modbus TCP, Modbus RTU, Devicenet, Profibus, Can Open |
Pressure Sensor: |
Modular internal 0-10"WC tube style (Std)
External 0-10"WC Non-Clogging (Opt)
Ranges other than 0-10"WC available |
Area Classification: |
Ordinary locations (pending)
Hazardous areas (pending) |
General: |
Circuit boards conformal coated for protection against dust, moisture & corrosives |
Brochure | Application Review Form | Contact |