Pressure Transmitters: Model DP 20T and SP 20T
Transmitter |
|
Configuration: |
Differential Pressure (Model DP 20T), Static Pressure (Model SP 20T) |
Supply Voltage: |
+15 to 40VDC |
Output: |
4-20mA, 2-wire |
Range: |
0 - 10” WC Std, 0-20", -10 to +10"WC and other ranges Opt |
Accuracy: |
Total Error <1.5% FS
Based on zeroing at ambient. Zeroing at temperature reduces error. |
Response Time: |
500 microseconds |
Resolution: |
Infinite |
Action: |
Positive at diaphragm Std, negative at diaphragm & bidirectional Opt |
Proof Pressure: |
100” WC for 0-10” WC range, higher consult factory |
Process Temperature: |
-13F (-25C) to 250F (120C), Std
-13F (-25C) to 450F (232C), Opt
Process temperatures over 250F require thermal isolation mount |
Housing: |
316SS NEMA 4X equivalent Std |
Diaphragm: |
Ceramic, Other Opt |
Process Mount: |
Tri-Clamp, 2" Std
Tri-Clamp, 2" with thermal isolation mounting extension, Opt |
Process Media: |
Compatible with most gases and particulate |
Area Classification: |
Ordinary locations, Std
Class I, II, III, Div I, II All groups, CSA Approved Opt |
Brochure | Application Review Form | Manual | Contact |