Particulate Monitor: EM 30 LGX
Control Unit |
|
Power supply: |
115/230VAC 50/60Hz Std (6 Watts max) 24VDC Opt |
Resolution (Range): |
5.0pA (0 to 5000pA) Std 0.5pA (0 to 5000.0pA) Opt |
Outputs: |
2 Relay (SPST 5A@240VAC) Std 1 Isolated 4-20mA Opt |
Enclosure: |
NEMA 4X Aluminum Std Other Opt |
Temperature: |
-13F (-25C) to 160F (70C) |
User Interface: |
LCD with digital, analog & text display, 4 button membrane keypad |
Area Classification: |
Ordinary locations (CE Approved) Std
Ordinary locations (CSA Approved for use with Class I, II, III sensor) Opt |
General: |
Circuit boards conformal coated for long life in harsh environments |
Sensor
|
|
Housing: |
NEMA 4X Aluminum Std |
Probe Lengths: |
3, 5, 10, 15, 20, 30, 36" (Approximately 1/2 duct/pipe I.D.)
Extended nipples & rope sensors for large multicompartment baghouses |
Mounting: |
NPT, Tri-Clamp or Flange |
Wetted Materials: |
316SS and Teflon or Ceramic Std Hastelloy Opt |
Process Temperature: |
-40F (-40C) to 250F (120C) Std 450F (232C) Opt 800-1600F Opt |
Process Pressure: |
10PSI (0.69bar) Std, 100PSI (6.9bar) Opt, 1000PSI (69bar) Opt |
Sensor Cable: |
300’ (100m) Max |
Area Classification: |
Ordinary locations (CE Approved) Std
Class I, II, III, Div I, II, All Groups (Intrinsically Safe, CSA Approved) Opt |
General: |
No special alignment, not affected by normal vibration |
Application Range
|
|
Particulate: |
Any type >0.3 micron - Conductive, non-conductive, moist, corrosive |
Minimum Detection Level: |
With 5.0pA resolution - Approx. 5-10mg/m3 (standard leak detection)
With 0.5pA resolution - Approx. 0.5mg/m3 (monitoring & analysis) |

Brochure | Application Review Form | Contact |